Charger

Renogy Wanderer 30A wiring diagram

Wanderer Li 30A PWM for 12V batteries only, with a 25V PV limit. Li selection and RS232 are present on the pictured version; no LOAD output. Optional Bluetooth uses BT-1.

Compatible systems
12 V
Rated output
30 A
PV open-circuit limit
25 V
Units

Wiring diagram

How the Wanderer 30A is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Renogy Wanderer 30A wiring example with 3 components: Reference PV, Wanderer 30A, House bank. 4 cable connections. Crossings are not junctions.Reference PV PV + to Wanderer 30A PV +: 6 mm² · 30 A fuse, 3 m one way. Wanderer 30A BATT + to House bank +: 10 mm² · 40 A fuse, 3 m one way. Reference PV PV − to Wanderer 30A PV −: 6 mm², 3 m one way. Wanderer 30A BATT − to House bank −: 10 mm², 3 m one wayReference PV PV + to Wanderer 30A PV +: 6 mm² · 30 A fuse, 3 m one wayWanderer 30A BATT + to House bank +: 10 mm² · 40 A fuse, 3 m one wayReference PV PV − to Wanderer 30A PV −: 6 mm², 3 m one wayWanderer 30A BATT − to House bank −: 10 mm², 3 m one way360 W reference PV arrayReference PVPV +PV +PV −PV −Renogy Wanderer 30AWanderer 30APV +PV +PV −PV −BATT +BATT +BATT −BATT −12 V 200 Ah house bankHouse bank++−−6 mm² · 30 A fuse10 mm² · 40 A fuse6 mm²10 mm²
Renogy Wanderer 30A wiring example with 3 components: Reference PV, Wanderer 30A, House bank. 4 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

12 V system

Wire
10 mm² · 8 AWG
Example fuse
40 A
Design current
30 A
Voltage drop
2.7%

Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

Supporting parts

  1. 6.1 m total of 10 mm² (8 AWG) marine cable
  2. Terminations for 10 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 40 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. Version 1.1), checked 2026-10-01. Manufacturer documentation →

Which Wanderer is covered?

The catalog photograph identifies the Wanderer Li 30 A, with a blue Li selection and an RS232 port. These notes therefore use the RNG-CTRL-WND30-LI manual. An older Wanderer without Li selection or RS232 needs its own instructions.

This is a PWM controller, despite the catalog ID beginning with “mppt”. It works with a 12 V battery only, and the specification table limits PV voltage to 25 V. Use an array suited to a 12 V PWM system and check its cold-weather Voc. A wattage description alone does not establish that array current and voltage are acceptable.

How do the terminals map?

The four main terminals correspond directly to PV + / PV − and BATT + / BATT −. The optional temperature-sensor connection and RS232 communications port are not shown in Crimp. This controller has no separate LOAD output; house loads require their own protected battery distribution.

Connect the battery first and then the solar panel. The controller’s terminals clamp stripped conductors; fully open each clamp before insertion and secure the conductor without forcing the screw. A terminal that looks open can still have its clamp raised against the cable entry.

What protection and cable limits apply?

Renogy specifies a 30 A controller-to-battery fuse in the fusing section. The largest terminal size is 8 AWG / 10 mm². Select the conductor for the actual circuit length and installation, and place battery-circuit protection at the source. PV fusing is based on array short-circuit current and the panel’s protection requirements, not an assumed 30 A solar current.

No reliable numeric tightening torque is given in this manual. The enclosure is IP20, so install it dry and vertically, with 150 mm above and below for ventilation. Do not put it in a sealed flooded-battery compartment.

How is the battery type selected?

Hold the gray button for about seven seconds until the type LED flashes, press it to select, and let the flashing stop to save. Green is sealed, orange gel, red flooded, and blue lithium. Confirm the separate type indicator rather than interpreting the PV or battery-status LED as chemistry.

The Li preset is intended for a 12.8 V LFP battery, with 14.2 V default boost and no float/equalization. An optional BT-1, connected through RS232, allows supported parameter changes. It is not built-in Bluetooth, and the battery’s approved charging voltage and temperature limits still govern.

Fit check

Connect it to the rest of your system.

Describe your setup to draft a system with Wanderer 30A connected. Review the selected parts and cable lengths, then edit the diagram in Crimp.

The model only picks parts and draws the connections. Every wire size and fuse rating still comes from Crimp's own sizing, never from the model.

Enable JavaScript to describe your system.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Wanderer Li 30A PWM for 12V batteries only, with a 25V PV limit. Li selection and RS232 are present on the pictured version; no LOAD output. Optional Bluetooth uses BT-1.

Compatible systems
12 V
Rated output
30 A
Planning charge current
30 A
PV open-circuit limit
25 V

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

PV +

positive · input

35 A

PV −

negative · input

35 A

BATT +

positive · output

30 A

BATT −

negative · output

30 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works