Epever Tracer 4210AN wiring diagram
Tracer4210AN: 40A MPPT, 520W at 12V / 1040W at 24V. PV Voc limits are 100V at minimum temperature and 92V at 25°C; array Isc is limited to 40A. Lithium bank voltage requires manual selection.
- Compatible systems
- 12 V / 24 V
- Rated output
- 40 A
- PV open-circuit limit
- 100 V
Wiring diagram
How the Tracer 4210AN is wired.
Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.
Cable sizing for this example
Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.
3 m one way
12 V system
- Wire
- 16 mm² · 6 AWG
- Example fuse
- 50 A
- Design current
- 40 A
- Voltage drop
- 2.2%
Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.
Run-length and manufacturer assumptions
The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.
Supporting parts
- 6.1 m total of 16 mm² (6 AWG) marine cable
- Terminations for 16 mm² cable, matched to the equipment's screw terminals, leads or studs
- 50 A fuse and holder on the positive run
- Heat-shrink, strain relief and terminal boots sized to the cable
Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.
Installation notes
Before you install.
Open a question for model-specific guidance and sources.
Verified against the manufacturer's documentation (rev. V2.3), checked 2026-10-01. Manufacturer documentation →
Which Tracer is covered?
The Tracer4210AN is a 40 A MPPT charger for 12 or 24 V batteries. This walkthrough uses the manufacturer's V2.3 manual distributed in the SV200 software download. Its rated charging power is 520 W at 12 V / 1040 W at 24 V. The 40 A figure also appears as the maximum PV input current in the wiring table; the catalog's former 50 A PV-terminal value was too high for this source.
What do the terminal pairs do?
PV + / PV − connect the array and BATT + / BATT − connect the house battery. The physical unit also has a 40 A LOAD pair, a temperature-sensor connection, chassis grounding point, and RS485 connector, omitted from the simplified drawing. It is a common-negative controller. Inverters must connect directly to a separately protected battery branch, not the load output.
The wiring table, printed page 10 lists 16 mm² / AWG 6 for the 4210AN battery/load wiring and maximum PV wire size. Cable length and voltage drop still need checking. The reviewed manual refers to tightening torque but supplies no numerical value; obtain the hardware-specific requirement rather than borrowing another manufacturer's torque.
Which protection and connection order apply?
The installation instructions, printed page 12 require a battery fuse 1.25–2 times rated current, equivalent to 50–80 A for this 40 A model, within 150 mm of the battery and coordinated with the cable. Keep disconnects open while wiring. Connect battery, then load, then PV; disconnect in reverse order. Confirm detected battery voltage before applying solar.
How is the array sized?
The specification table distinguishes 100 V Voc at the minimum operating temperature from 92 V at 25°C. These temperature qualifiers were reversed in the old catalog description. Also check the 40 A array Isc limit and the battery voltage +2 V to 72 V MPPT range. Charge-current clipping does not make excessive Voc or input current acceptable.
What must be configured and checked?
Select the battery type and charging parameters through the supported controls. Lead-acid voltage can be recognized automatically, but lithium system voltage must be set explicitly. Lithium temperature compensation is zero; correct chemistry selection does not replace the BMS or battery temperature restrictions. Verify equalization behavior before connecting a chemistry that cannot tolerate it.
Mount with 150 mm clearance above and below and adequate airflow, outside a sealed battery compartment. The enclosure is IP30, so keep it dry. Inspect polarity, actual battery voltage, charging state, and load-disconnect behavior after commissioning.
Fit check
Connect it to the rest of your system.
Describe your setup to draft a system with Tracer 4210AN connected. Review the selected parts and cable lengths, then edit the diagram in Crimp.
The model only picks parts and draws the connections. Every wire size and fuse rating still comes from Crimp's own sizing, never from the model.
Enable JavaScript to describe your system.
Technical reference
Specifications and terminal map.
Check the model, ratings and connection points against your own unit before choosing installation hardware.
Catalog specification
Tracer4210AN: 40A MPPT, 520W at 12V / 1040W at 24V. PV Voc limits are 100V at minimum temperature and 92V at 25°C; array Isc is limited to 40A. Lithium bank voltage requires manual selection.
- Compatible systems
- 12 V / 24 V
- Rated output
- 40 A
- Planning charge current
- 40 A
- PV open-circuit limit
- 100 V
Terminal map
Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.
PV +
positive · input
PV −
negative · input
BATT +
positive · output
BATT −
negative · output
Sources and sizing method
Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.
Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.