Phoenix Smart IP43 12/50

Victron Phoenix IP43 50A wiring diagram

Pictured universal-input Smart IP43 12/50 (1+1): 50A total, including a starter output limited to 4A. Input 85–250 VAC, startup from 90V and full power from 100V. The starter connection is omitted from the symbol.

Rated output
50 A
Units

Wiring diagram

How the Phoenix 50A is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Victron Phoenix IP43 50A wiring example with 3 components: Phoenix 50A, Battery disconnect, House bank. 3 cable connections. Crossings are not junctions.Phoenix 50A BATT + to Battery disconnect A: 16 mm² · 70 A fuse, 1.5 m one way. Phoenix 50A BATT − to House bank −: 16 mm², 1.5 m one way. Battery disconnect B to House bank +: 16 mm² · 70 A fuse, 30 cm one wayPhoenix 50A BATT + to Battery disconnect A: 16 mm² · 70 A fuse, 1.5 m one wayPhoenix 50A BATT − to House bank −: 16 mm², 1.5 m one wayBattery disconnect B to House bank +: 16 mm² · 70 A fuse, 30 cm one wayVictron Phoenix IP43 50A. The main-output example uses 16 mm² cable: 1.5 m from charger to disconnect plus a 0.3 m battery-positive lead, and a 1.5 m negative return (3.3 m total circuit). Both paths fit the manual's through-3 m recommendation. Its table assumes at least 90°C insulation, open unbundled routing at 30°C and at most 3% voltage drop. The displayed fuse is a planning result, not a manufacturer-specified rating; verify battery-side protection, fault-current capacity and the actual installation. AC, the auxiliary output and control wiring are not connected.Phoenix 50ABATT +BATT +BATT −BATT −Main Battery SwitchBattery disconnectAB12 V 200 Ah AGM placeholder bank. Example bank only: select the correct charger profile and confirm the actual battery's capacity, charging-current acceptance, voltage and temperature limits. Placeholder current limits are not manufacturer battery specifications.House bank++−−16 mm² · 70 A fuse16 mm²16 mm² · 70 A fuse
Victron Phoenix IP43 50A wiring example with 3 components: Phoenix 50A, Battery disconnect, House bank. 3 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.

The main-output example uses 16 mm² cable: 1.5 m from charger to disconnect plus a 0.3 m battery-positive lead, and a 1.5 m negative return (3.3 m total circuit). Both paths fit the manual's through-3 m recommendation. Its table assumes at least 90°C insulation, open unbundled routing at 30°C and at most 3% voltage drop. The displayed fuse is a planning result, not a manufacturer-specified rating; verify battery-side protection, fault-current capacity and the actual installation. AC, the auxiliary output and control wiring are not connected. Manufacturer installation manual

Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

1.5 m one way

12 V system

Wire
16 mm² · 6 AWG
Example fuse
70 A
Design current
50 A
Voltage drop
1.4%

Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

The main-output example uses 16 mm² cable: 1.5 m from charger to disconnect plus a 0.3 m battery-positive lead, and a 1.5 m negative return (3.3 m total circuit). Both paths fit the manual's through-3 m recommendation. Its table assumes at least 90°C insulation, open unbundled routing at 30°C and at most 3% voltage drop. The displayed fuse is a planning result, not a manufacturer-specified rating; verify battery-side protection, fault-current capacity and the actual installation. AC, the auxiliary output and control wiring are not connected. Manufacturer installation manual

Supporting parts

  1. 3 m total of 16 mm² (6 AWG) marine cable
  2. Terminations for 16 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 70 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. Rev 10 — 09/2026), checked 2026-10-19. Manufacturer documentation →

Which Smart IP43 is covered?

These notes cover the Smart IP43 12/50 (1+1), 120–240 V version visible in the catalog photograph. It supplies up to 50 A total to nominal 12 V batteries. The current manual specifies 85–250 VAC, startup from 90 VAC and full power from 100 VAC. Older 230 V-only Phoenix units need their matching instructions; the family name alone does not make their input range or auxiliary rating identical.

How do the outputs map?

BATT + / BATT − represent the main output. The catalog photo shows a 1+1 version, whose separate starter connector is omitted from this symbol. The current universal-input manual specifies 4 A maximum at the starter output, with the combined main-plus-starter current limited to the charger rating. Do not infer 3 A from older Phoenix-family descriptions or use this small output as a second full-power charger.

AC L / N / earth describe the IEC mains inlet and protective-earth connection. The symbol omits remote H/L, programmable relay, and VE.Direct. Use the correct mains cord with its retainer and an earthed outlet. The remote connector can receive a compatible BMS charge-permission control; it does not carry charging current.

How does the Smart IP43 12/50 synchronize with another charger?

Compatible chargers synchronize their charge stages through Bluetooth VE.Smart Networking. Connect them to the same battery bank, use the same charge settings, and keep them within Bluetooth range. The synchronization instructions explain that this does not equalize each charger's output current or set a combined current limit. With compatible solar and mains chargers together, solar is not automatically prioritized.

VE.Direct provides GX monitoring and control; remote H/L enables or disables charging. Neither connection alone configures a VE.Smart network. A GX used only for logging can coexist with VE.Smart; check Victron's networking limitations when a GX also controls charging. These data and control connections are omitted from the Crimp symbol.

What cable and protection are specified?

The printed page 19 table recommends 16 mm² through 3 m one way; longer listed runs are not recommended with the supported terminal size. These values assume at least 90°C insulation, open unbundled routing at 30°C, equal positive/negative lengths, and a 3% voltage-drop limit. They do not approve the same cable in every conduit or engine space.

Main DC terminals accept up to 16 mm² and tighten to 2.4 N·m. Fit suitable protection close to each battery positive. This manual's wiring diagrams require fuses/breakers but do not give a universal model-specific fuse amperage; select the rating with the installed conductor and battery fault current rather than borrowing another charger family's table.

The editable main-output example uses 16 mm² cable, with 1.5 m to the disconnect plus 0.3 m to battery positive, and a 1.5 m negative return. That is 1.8 m on the positive path and 3.3 m around the complete circuit, within the table's length range. Include every cable segment when adapting it. The displayed fuse remains a planning result to verify for the actual installation; it is not a fuse rating specified by Victron for this model.

What must be set before charging?

Select battery chemistry, charge voltage/current, and any required BMS control before use. Low mode limits this model to 25 A. Normal mode is 14.4 V absorption, 13.8 V float and 13.2 V storage; lithium uses its own preset without lead-acid temperature compensation. Configure all banks for one compatible charging profile. Remote control and the programmable relay have distinct functions; a relay signal is not a substitute for wiring the charge-disable input correctly.

How is the installation checked?

Mount vertically, terminals down, with 100 mm ventilation space above and below, on a nonflammable surface. Use a protected, dry location away from battery gases. Verify each bank's polarity and charging voltage, then test the configured current limit and any BMS stop command. The specification table rates full current through 40°C; heat and connected loads reduce charging headroom.

Fit check

Connect it to the rest of your system.

Describe your setup to draft a system with Phoenix Smart IP43 12/50 connected. Review the selected parts and cable lengths, then edit the diagram in Crimp.

The model only picks parts and draws the connections. Every wire size and fuse rating still comes from Crimp's own sizing, never from the model.

Enable JavaScript to describe your system.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Pictured universal-input Smart IP43 12/50 (1+1): 50A total, including a starter output limited to 4A. Input 85–250 VAC, startup from 90V and full power from 100V. The starter connection is omitted from the symbol.

Rated output
50 A
Planning charge current
47 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

AC L

neutral · input

16 A

AC N

neutral · input

16 A

AC ⏚

ground · bidi

16 A

BATT +

positive · output

50 A

BATT −

negative · output

50 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with Phoenix 50A.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Start drawing, sizing and checking without an account. Your drawing saves in this browser. See Pricing for the equipment allowance and the one-time export offer available to you.